Quick answer

A drainage fixture unit (DFU) is a code-assigned number that rates how much load one plumbing fixture puts on a drain, so the units from every fixture on a pipe can be added up and checked against the largest load that pipe size is allowed to carry.

It is a load factor, not gallons. A lavatory is 1 DFU and a 1.6-gallon tank toilet in a home is 3 DFU under the 2025 California Plumbing Code; other codes use their own tables.

Quick facts

The key facts about Drainage Fixture Unit (DFU), with sources:

What it sizes
Drain branches, stacks, building drains, sewers and many vents 46
Unit type
A load factor on an arbitrary scale, not a flow in gpm 5
Lavatory (2025 CPC, private)
1.0 DFU 1
1.6 gpf tank toilet (2025 CPC, private)
3.0 DFU 1
Continuous flow (2025 CPC)
2 DFU for each gpm 3
Intermittent flow (2025 CPC)
Up to 7½ gpm = 1 DFU, up to 15 = 2, up to 30 = 4, up to 50 = 6 2
Origin
Roy B. Hunter, National Bureau of Standards, 1940 5

Key takeaways

  • A DFU is a weight, not a flow: it lets plumbers add up very different fixtures on one scale and size the drain for the total.
  • Each code publishes its own DFU table; the 2025 California Plumbing Code (UPC-based) and IPC-based codes do not always agree.
  • The same fixture can carry more DFUs in public or assembly buildings, where it is used harder.
  • Pumps and equipment are converted from gpm: 2 DFU per gpm for continuous flow in the CPC.
  • DFUs size drains. Supply pipes use a separate number, the water supply fixture unit.

What a drainage fixture unit measures

Drains are not sized by adding up gallons. A toilet dumps a short, heavy surge; a lavatory trickles; a washing machine pumps out for minutes. They rarely all drain at once. Codes need a way to compare them, so each fixture gets a weight, and the weights add up.

That idea comes from Roy B. Hunter’s 1940 report for the National Bureau of Standards.

He defined a fixture unit as a numerical factor that measures, on an arbitrary scale, the load-producing effect of one fixture of a given kind 5.

He also warned that it is not a definite unit of flow 5.

Hunter noted that his probability method had only limited use for drains, and that a toilet should carry the same drainage weight whether it has a tank or a flush valve 5.

Modern codes built their DFU tables on that base. In the 2025 California Plumbing Code (CPC), the minimum size of every drain is set from the total fixture units connected to it, plus length for vertical pipes 4.

DFU vs. WSFU

A drainage fixture unit rates the load a fixture puts on the drain. A water supply fixture unit (WSFU) rates the demand it puts on the supply pipes and water meter. Same idea, different tables, different pipes. Never add one to the other.

How a DFU total turns into a drain pipe size

  1. List every fixture on the pipe. Count only what drains into that branch, stack or building drain.
  2. Look up each DFU value. In the CPC, values depend on the fixture and on private, public or assembly use 1.
  3. Convert pumps and equipment. Intermittent flow uses the gpm bands in Table 702.2; continuous flow counts 2 DFU per gpm 23.
  4. Add the total. The sum is the load on that pipe.
  5. Check the code’s capacity table. The total must not exceed what the chosen pipe size and slope may carry; in the CPC that is Table 703.2 4.
  6. Use it for vents too. IPC-based codes also size stack vents, wet vents and single-stack systems from DFU load 6.
Process From fixture list to drain size
  1. List fixturesOn the pipe being sized
  2. Assign DFUsFrom your adopted code table
  3. Add pumpsgpm converted to DFU
  4. Total the loadSum of all units
  5. Pick the pipeSmallest size whose limit covers the total

The capacity table, slope and local amendments decide the final size; this is the order of the check, not a design. Source: [4] [2] [3]

How many DFUs common home fixtures carry (2025 CPC)

Excerpt from 2025 CPC Table 702.1. Assembly occupancies use higher toilet values (6.0 or 8.0). IPC and IRC tables differ; use your adopted code.
FixtureMinimum trap size (in)Private usePublic use
Lavatory1¼1.0 11.0 1
Bathtub or tub/shower1½2.0 12.0 1
Shower, single head22.0 12.0 1
Kitchen sink, domestic (with or without disposer, dishwasher or both)1½2.0 12.0 1
Clothes washer standpipe23.0 13.0 1
Laundry sink1½2.0 12.0 1
Floor drain22.0 12.0 1
Water closet, 1.6 gpf gravity tank33.0 14.0 1
Water closet, over 1.6 gpf gravity tank34.0 16.0 1

Example: adding up the DFUs for a two-bath house

This totals the drainage load for a typical two-bath home using the private-use values in 2025 CPC Table 702.1, plus one small condensate pump. The fixture list is an illustration; the values are from the code.

FixtureCountDFU eachSubtotal
Water closet, 1.6 gpf tank23.0 16.0
Lavatory31.0 13.0
Bathtub/shower12.0 12.0
Shower stall12.0 12.0
Kitchen sink (dishwasher drains through it)12.0 12.0
Clothes washer standpipe13.0 13.0
Condensate pump, 0.5 gpm continuous12 per gpm 31.0
Total on the building drain19.0 DFU
Formula Total drainage load on a pipe

Total DFU = Σ (fixture count × DFU value) + pump DFUs

DFU value
From your adopted code table, by fixture and occupancy
Pump DFUs
Continuous: 2 per gpm; intermittent: per Table 702.2 bands (2025 CPC)

Then compare with the pipe’s allowed load in the code’s sizing table 4.

Source: [1] [2] [3]

A plumber then checks 19 DFU against the building drain capacity for the chosen pipe size and slope in the adopted code’s table.

Note what is not here: the dishwasher is not counted separately, because the CPC kitchen sink value already covers it 1; and a house with three or more washers in one laundry area would rate each at 6 DFU for common piping 1.

The fixture unit calculator explains the supply-side method; drain sizing needs your code’s own tables.

Where DFU totals show up on plans, remodels and septic designs

On plans: commercial and multifamily drawings often carry a riser diagram with DFU totals written on each stack and building drain. Inspectors check those totals against the code table.

In remodels: adding a bathroom, a basement laundry or a second kitchen adds DFUs to an existing drain. If that drain was sized close to its limit, it may need to be upsized. Our plumbing rough-in page covers where these decisions get made.

In septic design: the CPC tells designers to count water closets as 6 DFU when sizing septic tanks under its Appendix H 1. On a house sewer quote, DFUs may be cited to justify a 3-inch or 4-inch line; see our sewer line repair service.

Why codes use DFUs and where they fall short

What it does well

  • Puts very different fixtures on one scale, so loads can be added 5.
  • Builds in the fact that fixtures rarely all drain at once 5.
  • Gives inspectors a simple, repeatable check.
  • Adjusts for heavier use in public and assembly buildings 1.
  • Handles pumps and equipment through gpm conversions 23.

Where it falls short

  • Values are copyrighted model-code tables that differ between codes.
  • They date from older, higher-flow fixtures; Hunter’s 1940 weights predate low-flow toilets 5.
  • A DFU says nothing about slope, pipe roughness or venting on its own.
  • Fixtures not in the table must be rated by trap size 1.
  • Large intermittent flows above 50 gpm are left to the local authority 2.

What a DFU count cannot tell you

It cannot tell you if an existing drain works. A pipe sized correctly on paper can still clog with grease, roots or a sag. For that, a sewer camera inspection tells you more than any table.

It is not a flow rate. Hunter’s own definition calls it a load factor, not a unit of flow 5. You cannot convert a DFU total into gallons per minute of drain capacity without the code’s sizing tables and slope.

It is not portable between codes. A toilet’s DFU and a pipe’s DFU limit come as a matched pair from one code. Mixing a value from one code with a capacity from another gives a meaningless answer.

Pumps are the other place people go wrong, because a pump that runs now and then is rated by band, not by the 2-per-gpm continuous rule. The four bands from Table 702.2 are below; above 50 gpm, the local authority decides 2.

Key figures Intermittent pump discharge converted to DFU (2025 CPC Table 702.2)
  • 1 DFUUp to 7.5 gpm
  • 2 DFUOver 7.5 to 15 gpm
  • 4 DFUOver 15 to 30 gpm
  • 6 DFUOver 30 to 50 gpm

Source: [2]

How DFUs affect the cost of a drain job

We do not list prices; fair numbers need dated local quotes.

DFUs drive cost indirectly, through pipe size. A higher total can push a branch, stack or building drain to the next pipe size, which means larger fittings, wider wall framing for stacks, and more trenching for a building sewer.

In a remodel, the biggest cost driver is whether added fixtures push an existing drain past its limit and force a replacement run, sometimes through a slab.

Design and permit work also cost time: plans for larger projects show DFU totals for review. For how drain and sewer jobs are priced, see our plumbing cost guide and the sewer repair or replace tool.

How a plumber uses DFUs on a permitted project

Drain sizing is permitted work. This is the general sequence a designer or licensed plumber follows.

  1. Confirm the code and edition. UPC-based and IPC-based tables differ; local amendments apply.
  2. Draw the drain layout. Every branch, stack and the building drain, with fixtures connected.
  3. Assign DFUs by occupancy. Private, public or assembly values 1.
  4. Add equipment loads. Pumps, ejectors and AC condensate by the continuous or intermittent rules 23.
  5. Size each segment. Use the capacity table and slope; vertical pipes also have length limits in the CPC 4.
  6. Size the vents. In IPC-based codes, stack vents, wet vents and single stacks are sized from DFU load 6.
  7. Submit and inspect. The inspector checks pipe sizes against the totals, then the drain test.

How to keep a drain within its design load

  • Before adding a fixture, ask what the drain it joins was sized for.
  • Do not tie a sump pump or ejector into a small branch without checking its gpm conversion 23.
  • Keep grease, wipes and debris out; a partly blocked pipe has less capacity than its DFU rating assumes.
  • Have old cast iron or clay lines scoped before adding a bathroom.
  • Keep cleanouts reachable for clearing; see our sewer cleanout page.

Ask this before a basement bath

Ask your plumber: what drain will this tie into, how many DFUs does it already carry, and what is its limit under our code? If the answer is “we will check,” that is fine. If it is “it will be fine,” ask again.

Which signs mean a drain is overloaded or undersized

  • Toilets gurgle or traps bubble when another fixture drains.
  • Water backs up into a tub or shower when the washer pumps out.
  • A lower-level fixture overflows when upstairs fixtures run.
  • Drains slow down after a remodel added fixtures.
  • Sewage odors near drains, which can mean a siphoned trap from poor venting.

Sewage backups are a health hazard

If sewage comes up through a floor drain or tub, stop using water in the house, keep children and pets away, and call a plumber. Do not enter flooded basements where water may reach outlets or appliances, and do not open a sealed ejector pit or sewer line yourself.

These signs also come from clogs and vent problems. A plumber can tell which with a camera and a look at the vent layout. Sewage backing up is urgent; see our plumbing emergencies guide or drain cleaning service.

Which codes set DFU values

California Plumbing Code, 2025 edition (UPC-based, in force 1 January 2026), §702.1 and Table 702.1: DFU values by fixture, trap size and occupancy, with notes on washer batteries (6 DFU each for three or more) and septic sizing (water closets at 6 DFU) 1.

CPC 2025 §702.2 and Table 702.2: intermittent flow converts by gpm band, with flows over 50 gpm set by the Authority Having Jurisdiction 2.

§702.3: continuous flow from pumps, ejectors and air conditioning counts 2 DFU per gpm 3.

§703.1–703.2: drain sizes come from total fixture units, and Table 703.2 gives limits by pipe size 4.

IPC-based codes: New York’s 2020 code, based on the IPC, sizes drains from Table 710.1(1) and horizontal branches and stacks from Table 710.1(2), and sizes several vent types from DFU load 6. Values differ from the UPC family.

Adoption: states and cities adopt one model code and amend it. Check the code your jurisdiction enforces and its edition before relying on any value. Rules here were checked on 2026-10-13.

How DFUs compare with WSFUs, flow rate, trap size and slope

MeasureWhat it ratesUsed to sizeMain difference
Drainage fixture unit (DFU)Load on the drain 5Drains, stacks, sewers, vents 46Weight, not flow
Water supply fixture unit (WSFU)Demand on supply pipesWater service, meter, distributionSeparate table and conversion to gpm
Flow rate (gpm)Actual water flowFixture ratings, pumpsA real flow; pumps convert to DFU 3
Trap sizeFixture outlet diameterFixture drain and trap armSets DFU for unlisted fixtures 1
Pipe slopeFall per foot of runHorizontal drainsWorks with DFU limits; not a load

What people get wrong about DFUs

Myth One DFU equals one gallon per minute.
Reality It is a load factor on an arbitrary scale; Hunter said it is not a definite unit of flow 5.
Myth A low-flow toilet barely counts.
Reality In the CPC a 1.6 gpf tank toilet is still 3.0 DFU in a home, against 4.0 for a larger one 1; it is still among the heaviest home fixtures.
Myth A dishwasher adds its own DFUs at the kitchen sink.
Reality The CPC kitchen sink value covers sinks with or without a dishwasher or disposer 1.
Myth DFU values are the same everywhere.
Reality UPC-based and IPC-based codes publish different tables, and states amend them.
Myth DFUs only matter for drains.
Reality IPC-based codes size several vent types from DFU load too 6.
Chart Private-use DFU values for common fixtures

Under the 2025 CPC, a lavatory is 1 DFU, a bathtub and a kitchen sink 2 each, a clothes washer standpipe and a 1.6 gpf tank toilet 3 each, and a larger tank toilet 4.

Private-use DFU values for common fixtures (drainage fixture units)
ItemValue (drainage fixture units)
Lavatory 1 DFU
Bathtub or tub/shower 2 DFU
Kitchen sink, domestic 2 DFU
Clothes washer standpipe 3 DFU
Water closet, 1.6 gpf tank 3 DFU
Water closet, over 1.6 gpf tank 4 DFU

Data period: 2025 California Plumbing Code, Table 702.1

Source: [1]

Which code your state uses changes the numbers

The single biggest local variable is the model code. California adopts the UPC as the California Plumbing Code with state amendments, so CPC Table 702.1 applies there 1.

New York and many other states adopt the IPC family, which uses its own DFU and capacity tables 6. Cities and counties then amend on top.

That is why a DFU value copied from a forum or another state can be wrong for your project. Ask your building department which code and edition it enforces.

When DFUs matter to you and what to ask your plumber

They matter when you add a bathroom, laundry, basement bar or second kitchen, when you convert a garage or build an ADU, and when you review a plumbing bid that says a drain must be upsized.

Your next step: give your plumber the full list of fixtures you plan, and ask which drain each one joins and whether that drain has room. If a bid calls for a new building drain, ask to see the DFU total and the code table behind it.

Decision guide Does your project need a DFU check?
If Replacing a fixture with the same type
Then Usually no change in DFU load 1
If Adding a bathroom or laundry
Then Yes: new DFUs on an existing drain
If Adding a sump, ejector or condensate pump
Then Yes: convert gpm to DFU 23
If Building with three or more washers in one area
Then Yes: rated 6 DFU each for common piping 1

Source: [1] [2] [3]

Questions about Drainage Fixture Unit (DFU)

How many DFU is a shower?

Under the 2025 California Plumbing Code, a shower with a single-head trap is 2.0 DFU in both private and public use, with a 2-inch minimum trap.

A bathtub or combination tub and shower is also 2.0 DFU but with a 1½-inch minimum trap. IPC-based codes publish their own values, so check the code your area adopted.

How many DFU is a toilet?

It depends on the code and the toilet. Under the 2025 California Plumbing Code, a 1.6-gallon tank toilet is 3 DFU in a home and 4 in public use; a toilet using more than 1.6 gallons is 4 DFU private and 6 public. IPC-based codes publish their own values.

How do you calculate DFU for a house?

List every fixture that drains into the pipe, look up each one’s DFU in your adopted code table, add pumps by their gpm conversion, and total it. For example, two tank toilets, three lavatories, a tub, a shower, a kitchen sink and a washer total 18 DFU using 2025 CPC private values.

What is the difference between DFU and WSFU?

DFU rates the load on the drain system and sizes drains, stacks, sewers and vents. WSFU, the water supply fixture unit, rates demand on the supply pipes and sizes the water service and meter. Each has its own table, and they are never added together.

How many DFU is a kitchen sink with a dishwasher?

In the 2025 California Plumbing Code, a domestic kitchen sink is 2 DFU with or without a disposer, dishwasher or both, so the dishwasher is not counted separately when it drains through the sink. A dishwasher with its own independent drain is also 2 DFU.

How are sump pumps counted in fixture units?

By their flow. The 2025 CPC counts continuous flow, such as from a pump, ejector or air conditioner, at 2 DFU per gallon per minute. Intermittent flow uses bands: up to 7½ gpm is 1 DFU, up to 15 is 2, up to 30 is 4, and up to 50 is 6.

Are DFU values the same in the IPC and UPC?

No. Both codes use the fixture unit idea from Hunter’s 1940 work, but they publish different tables for fixtures and pipe capacities. States adopt one and often amend it. Always use the values and the capacity table from the same adopted code.

Do DFUs affect vent sizing?

Yes, in IPC-based codes. New York’s 2020 code, based on the IPC, sizes stack vents, horizontal wet vents and single-stack systems using the DFU load they serve. Vent rules differ by code, so ask what your jurisdiction uses.

Who invented the fixture unit?

Roy B. Hunter of the National Bureau of Standards, now NIST, in his 1940 report Methods of Estimating Loads in Plumbing Systems. He defined a fixture unit as a load factor on an arbitrary scale and noted that for drains a toilet carries the same weight with a tank or a flush valve.

Sources

  1. California Plumbing Code (Title 24, Part 5), 2025 edition, §702.1 Trap Size and Table 702.1 Drainage Fixture Unit Values (GoCodebook public copy), retrieved .
  2. California Plumbing Code, 2025 edition, §702.2 Intermittent Flow and Table 702.2 (GoCodebook public copy), retrieved .
  3. California Plumbing Code, 2025 edition, §702.3 Continuous Flow (GoCodebook public copy), retrieved .
  4. California Plumbing Code, 2025 edition, §703.1 Minimum Size and §703.2 Maximum Number of Fixture Units (GoCodebook public copy), retrieved .
  5. Roy B. Hunter, Methods of Estimating Loads in Plumbing Systems, NBS Building Materials and Structures Report BMS65 (December 16, 1940), retrieved .
  6. New York Department of State, Code Outreach Program Issue 2021-05: Plumbing Vents (2020 Plumbing Code of New York State, May 7, 2021), retrieved .

Expert review

Written by the HyrePlumber Research team. Not yet reviewed by an outside expert. We say so rather than imply a review that has not happened; see our editorial policy.

How the numbers were checked: DFU values and flow conversions are from public copies of the 2025 California Plumbing Code (in force 1 January 2026; Table 702.1, Table 702.2 and §702.3 re-read on 2026-10-13 and unchanged from 2022) §702.1–702.3 and §703.1–703.2.

The CPC Table 703.2 pipe capacity values could not be read from the public copy and are not reproduced. IPC-family use is described from New York’s 2020 code outreach bulletin, because codes.iccsafe.org was not readable.

The fixture unit concept and history are from Hunter’s 1940 NBS report. The house example uses an illustrative fixture list with code values. No prices are given.

Suggest a correction. We fix errors and say what changed.